Can I read the working setpoint during a ramp via Modbus on CAL controllers?

-         If you want to read the changing setpoint during the ramp section of the Ramp-Soak feature of a CAL 3300, 9300 or 9400 controller, the parameter is 522dec (0x020A hex).

This register also to valid to read the effective set point of CAL 9500P while running a profile

-         Test message send operation completed

-          

-         Sending Test Message

-          

-          

-         11:19:56 Sent: 03,03,02,0A,00,01,A4,52

-          

-         11:19:56 Received: 03,03,02,01,64,C1,FF

-          

-         _______________

-          

-         Test message send operation completed

-          

-         Sending Test Message

-          

-          

-         11:28:28 Sent: 03,03,02,0A,00,01,A4,52

-          

-         11:28:29 Received: 03,03,02,02,0E,41,20

-          

-         _______________

-          

-         Test message send operation completed

-          

-         Sending Test Message

-          

-          

-         11:31:23 Sent: 03,03,02,0A,00,01,A4,52

-          

-         11:31:23 Received: 03,03,02,02,48,C0,D2

-          

-         _______________

-          

-         Test message send operation completed

-          

-         Sending Test Message

-          

-          

-         11:31:39 Sent: 03,03,02,0A,00,01,A4,52

-          

-         11:31:39 Received: 03,03,02,02,4E,40,D0

-          

-         _______________

-          

-         Test message send operation completed

-          

-         Sending Test Message

-          

-          

-         11:32:04 Sent: 03,03,02,0A,00,01,A4,52

-          

-         11:32:05 Received: 03,03,02,02,56,40,DA