Understanding CAL"Offset" Parameter
- The Level 1 Offset parameter sets the proportional power biasing (similar to Manual Reset/Bias in West products and Working Point in PMA products).
- For CAL, the values can be +/- 0.5 x the proportional band. If BAND was 30, OFFSET could be -15 to +15.
- At the maximum possible +ve value of Offset, proportional power when PV =SP is 100%
- At the maximum possible -ve value of Offset, proportional power when PV =SP is 0%
- When Offset = 0, proportional power when PV =SP is 50%
- The attached spreadsheet illustrates this.
- Offset also affects the CAL controllers’ derivative band in a similar way.
- see also Solution "Understanding the CAL Derivative and DAC Parameters
- Applies to CAL3200, 3300, 9300, 9400 and 9500