Blue Control will not communicate with ProVU, Pro96 or EC44 via the Configurator Lead
The Blue Control communication settings change depending on what is fitted into option slot A of the instrument.
The speed selected in Blue Control when uploading or downloading must be:
Slot A Empty = 19200
Slot A Fitted with Digital Input = 19200
Slot A Fitted with Ethernet Comms = 9600
Slot A Fitted with Auxiliary (RSP) Input = 4800
For all of the above options: Start and Stop bits must be 1, and Data bits 8. Parity must be None and address 1
Slot A Fitted with RS485 Comms = All settings must match the RS485 comms set in the Comm Settings in Configuration Mode.
This information is shown in the “Configuring The Connection” in the manual.